Application:
YFD400A contactor is applicable for electric control system of communication power supply and other electronic control devices
Brief Technical Data:
| Number | Type and parameters | Coil and rated volt of contact circuit(v) | |||||||
| 12 | 24 | 30 | 36 | 40 | 48 | 72 | 80 | ||
| 1 | YFD400A coil hold current(A) | |
0.3 | |
|
|
0.12 | |
|
| 2 | main rated load current of contact circuit:Resistive loadて=1ms,inductive load60%Icfor resistive load, | YFD400A | |||||||
| 400A | |||||||||
| 3 | voltage | 50Hz 1000V AC 1min | |||||||
| 4 | Operating time | Pickup(contact makes):≯30ms, Release(contact breaks):≯30ms | |||||||
| 5 | Action characteristic | Pickup(contact makes):≯66%Us, Release(contact breaks):≯30%Us,≮5% Us | |||||||
| 6 | Mechanical life | 300 thousand times | |||||||
| 7 | Electric life | Resistive load(て=1ms):lle,5 million times,inductive load(DC-5): 60%le for Resistive load ,2million times | |||||||
Notice:
1. Specifications subject to change as the custom request
Environmental condition:
1. Ambient temperature:-25~+40℃
2. Altitude range:0~2000m
3. Max.relative humidity90% at 25℃
4. Vibration:10~50Hz,10m/s2
5. Shock:30m/s2
6. Installation method:anywhere
7. Voltage fluctuating:0.7~1.1Ue
8. Duty:8h continuous
Configurational mounting diagram:
Circuit diagram:
Nomination(nomogram)